For selecting WELL-X-TROLs for a different running time than ESP I or ESP II, and/or at pressure ranges the same or different than 20/40,30/50, 40/60:
THINGS YOU MUST KNOW
1, System flow rate (pump capacity or discharge) GPM
. Min. . Psig. Psig . ESPVol. |
2. Desired running time, in minutes and fractions of minutes (1.5 min. = 1 min. 30 sec ) 3. Pump cut-in. in gauge pressure 4. Rump cut-out, in gauge pressure CALCULATING TANK SIZE 5. Multiply Line 1 by Line2 and enter ESP Volume |
, P. F. |
, Gals. |
Refer to Table 2 and select WELL-X-TROL model that is greater than Line 7 tor “Total Volume» and Line 5 is less than “Maximum ESP Volume" |
THINGS YOU MUST KNOW 1. System flow rate (pump delivery) |
12.5 GPM |
1.5 Min. 25 Psig 45 Psig |
2. Desired running time, in minutes and fractions of minutes(1.5 min. = tmin.30sec.) |
3. Pump cut-in. in gauge pressure |
18.8 ESPVol. 34 P. F. |
7. Divide Ltne 5 by Line 6 and enter minimum total WELL-X-TROL volume |
55.2 Gals |
WX-251 |
FIGURE 8.35 ■ Pressure tank sizing form. (Courtesy of McGraw-Hill) |
|
|||
|
|||
|
|||
|
|||
|
|
||
|
|||
|