RISER DRAWINGS

Riser drawings are used when figuring out drainage systems, just as they are used with vent systems. I want to give you some sample riser diagrams to look over. The drawings will show you what your drawings might look like. Drains are drawn with solid lines, while vents are indicated by broken lines.

RISER DRAWINGS

FIGURE 4.26 ■ Wet venting top floor single bath group. (Courtesy of Standard Plumbing Code)

RISER DRAWINGS

FIGURE 4.27 ■ Wet venting top floor double bath back to back. (Courtesy of Standard Plumbing Code)

RISER DRAWINGS
RISER DRAWINGS

OR

 

SHOWERS

 

M N

 

RISER DRAWINGS
RISER DRAWINGS
RISER DRAWINGS

RISER DRAWINGS

RISER DRAWINGS

FIGURE 4.28 ■ Wet venting lower floors on multistory buildings. (Courtesy of Standard Plumbing Code)

RISER DRAWINGS

RELIEF VENTS A & В MAY CONNECT TO MAIN—„„

VENT ABOVE FIXTURES ON FLOOR ABOVE

-T—I

 

RELIEF VENTS REQUIRED-
914.1

 

SEE 715 UNLESS SIZED FOR A BUILDING DRAIN

 

RISER DRAWINGS
RISER DRAWINGS

FIGURE 4.29 ■ Riser diagram. (Courtesy of Standard Plumbing Code)

 

Подпись: DRAIN-AND-SEWER CALCULATIONS

RISER DRAWINGSRISER DRAWINGSRISER DRAWINGS

RISER DRAWINGS

4" MIN.

 

STACK VENT

 

i-1 1/4" MIN. I MAN VENT—»j

 

RISER DRAWINGS

1 1/2" MIN;

 

WET VENT 1 II

 

RISER DRAWINGS

REQUIRED VENT

 

‘klT U~i

 

REQUIRED VEfJT

 

WET VENT

 

1 1/4" MIN;

 

VENT NOT REQ

 

RISER DRAWINGS
RISER DRAWINGS
RISER DRAWINGS
RISER DRAWINGS

RISER DRAWINGS

RISER DRAWINGS

FIGURE 4.30 ■ Multistory wet venting. (Courtesy of Standard Plumbing Code)

RISER DRAWINGS

FIGURE 4.31 ■ Riser diagram. (Courtesy of Standard Plumbing Code)

 

Подпись: DRAIN-AND-SEWER CALCULATIONS

Q

SO

 

»I

о

 

Подпись: PLUMBER’S AND PIPE FITTER’S CALCULATIONS MANUAL

YOKE VENT
REQUIRED
SECTIONS
715.4 &
917.3

45’ MAX.
FROM
VERTICAL
TO PREVENT
FOULING

 

-SIZE FOR
NUMBER OF
FIXTURE UNITS
ABOVE OFFSET

FOR

OMISSION ________

SEE SEC. T
715.5

 

BLOWOUT FIXTURES REQUIRE INDIVIDUAL VENTS,7 BATTERY VENTING NOT PERMITTED. /

 

SIZE OF EACH SECTION OF VENT BASED ON FIXTURE UNIT LOAD.

 

RELIEF VENT REQUIRED, SEE 715.4
<St 917.3 {SIZE FOR MAIN VENT)

FOR OMISSION SEE
SEC. 715.5

H—-NO HORIZONTAL BRANCH CONNECTION 715.4

 

OFFSET OF MORE THAN 45* FROM VERTICAL SIZE AS FOR A BUILDING DRAIN. 715.4

 

-NO HORIZONTAL-1 BRANCH CONNECTION 715.4

 

SIZE FOR OFFSET AND TOTAL FIXTURE UNITS ON STACK

 

RISER DRAWINGS

4 /L

 

VENT FIXTURES BACK TO BACK IN BATTERY, 914.3

 

FIGURE 4.32 ■ Riser diagram. (Courtesy of Standard Plumbing Code)

 

RISER DRAWINGSRISER DRAWINGSRISER DRAWINGSRISER DRAWINGS

RISER DRAWINGS

VENT TERMINAL SEC. 904.2 AND 905

 

BATTERY WITH LOOP VENT

 

SIXTH FLOOR

 

RISER DRAWINGS

o4-o o4-o LrTJ

 

FIFTH FLOOR

 

4

 

RISER DRAWINGS

——

 

FOURTH FLOOR

 

RISER DRAWINGS
RISER DRAWINGS

BACK TO BACK IN BATTERY

 

THIRD FLOOR

 

RISER DRAWINGS
RISER DRAWINGS

SECOND FLOOR

 

RISER DRAWINGS

RISER DRAWINGS

RISER DRAWINGS

FIGURE 4.33 ■ Drainage waste and vent reference diagram. (Courtesy of Standard Plumbing Code)

RISER DRAWINGS

FIGURE 4.34 ■ Fixtures back-to-back in battery. (Courtesy of Standard Plumbing Code)

Updated: 15 ноября, 2015 — 1:11 дп