REMAINING TABLES

The remaining tables are different in content, but the procedures for using them are the same. Once you know the number of bedrooms and bathrooms for a dwelling, you can quickly and easily determine the minimum require­ments for a water heater. You have just seen how simple the tables are. When you have a water heater to size, just refer to the tables in this chapter (Fig. 7.4, to 7.10) or the tables in your local codebook.

Number of bedrooms

2

3

4

5

Storage capacity (gallons)

30

40

40

50

Input in Btuh

36,000

36,000

38,000

47,000

Draw (gallons per hour)

60

70

72

90

Recovery (gallons per hour)

30

30

32

59

FIGURE 7.4 ■ Water heating sizing table for gas heaters (minimum recommendations). Assume 2 to 21/2 bathrooms.

Number of bedrooms

2

3

4

5

Storage capacity (gallons)

40

50

50

66

Input in Btuh

4.5 KW

5.5 KW

5.5 KW

5.5 KW

Draw (gallons per hour)

58

70

72

88

Recovery (gallons per hour)

18

22

22

22

FIGURE 7.5 ■ Water heating sizing table for electric heaters (minimum recommendations). Assume 2 to 21/2 bathrooms.

Number of bedrooms

2

3

4

5

Storage capacity (gallons)

30

30

30

30

Input in Btuh

70,000

70,000

70,000

70,000

Draw (gallons per hour)

89

89

89

89

Recovery (gallons per hour)

59

59

59

59

FIGURE 7.6 ■ Water heating sizing table for oil-fired heaters (minimum recommendations). Assume 2 to 21/2 bathrooms.

Number of bedrooms

3

4

5

6

Storage capacity (gallons)

40

50

50

50

Input in Btuh

38,000

38,000

47,000

50,000

Draw (gallons per hour)

72

82

90

92

Recovery (gallons per hour)

32

32

40

42

FIGURE 7.7 ■ Water heating sizing table for gas heaters (minimum recommendations). Assume 3 to 31/2 bathrooms.

Number of bedrooms

3

4

5

6

Storage capacity (gallons)

50

66

66

80

Input in Btuh

5.5 KW

5.5 KW

5.5 KW

5.5 KW

Draw (gallons per hour)

72

88

88

102

Recovery (gallons per hour)

22

22

22

22

FIGURE 7.8 ■ Water heating sizing table for electric heaters (minimum recommendations). Assume 3 to 3V2 bathrooms.

Number of bedrooms

3

4

5

6

Storage capacity (gallons)

59

59

59

59

Input in Btuh

70,000

70,000

70,000

70,000

Draw (gallons per hour)

89

89

89

99

Recovery (gallons per hour)

59

59

59

59

FIGURE 7.9 ■ Water heating sizing table for oil-fired heaters (minimum recommendations). Assume 3 to 3V2 bathrooms.

Подпись: PLUMBER'S AND PIPE FITTER'S CALCULATIONS MANUAL

Column 1

Column 2

Buildings of ordinary tightness

Buildings of unusually tight construction

Condition

Size of opening or duct

Condition

Size of opening or duct

Appliance in unconfined2

space

May rely on infiltration alone.

Appliance in unconfined2 space:

Obtain combustion air from outdoors or from space freely communicating with outdoors.

Provide two openings, each having 1 sq. in. per 5,000 Btu/h input.

Appliance in confined4 space

1. All air from inside building

Provide two openings into enclosure each having one square inch per 1,000 Btu/h input freely communicating with other unconfined interior spaces. Minimum 100 sq. in. each opening.

Appliance in confined4 space:

Obtain combustion air from outdoors or from space freely communicating with outdoors.

1. Provide two vertical ducts or plenums: 1 sq. in. per 4,000 Btu/h input each duct or plenum.

2. Provide two horizontal ducts or plenums: 1 sq. in. per 2,000 Btu/h input each duct or plenum.

3. Provide two openings in an exterior wall of the enclosure: each opening 1 sq. in per 4,000 Btu/h input.

4. Provide one ceiling opening to ventilated attic and one vertical duct to attic: each opening 1 sq. in. per 4,000 Btu/h input.

2. Part of air from inside building

Provide two openings into enclosure3 from other freely communicating unconfined2 interior spaces, each having an area of 100 sq. in. plus one duct or plenum opening to outdoors having an area of 1 sq. in. per 5,000 Btu/h input rating.

3. All air from outdoors: Obtain from outdoors or from space freely communicating with outdoors.

Use of any of the methods listed for confined space in unusually tight construction as indicated in Column 2.

5. Provide one opening in enclosure ceiling to ventilated attic and one opening in enclosure floor to ventilated crawl space: each opening 1 sq. in. per 4,000 Btu/h input.

’For location of opening, see Section 1307(c).

2As defined in Section 122,

3When the total input rating of appliances in enclosure exceeds 100,000 Btu/h, the area of each opening into the enclosure shall be increased 1 sq. in. for each 1,000 Btu/h over 100,000,

4As defined in Section 104(h).

 

FIGURE 7.10 ■ Size of combustion air openings or ducts for gas-or liquid-burning water heaters. [Courtesy of Uniform Plumbing Code)

Подпись: WATER PUMPS

ome plumbers work their entire careers without ever having to know anything about water pumps. Other plumbers deal with pumps on a fre­quent basis. The difference is where the plumbers work. I’ve never worked in New York City, but I suppose there are not many water pumps to be installed or serviced. But where I live, in Maine, there are more homes served by private water wells than you can shake a stick at. When I lived in Virginia, there were plenty of water pumps, too. Some of the pumps are jet pumps and others are submersible pumps. The two are very different, even though they do the same job.

Jet pumps are at their best when used in conjunction with shallow wells, with depths of say 25 feet or less. Two-pipe jet pumps can be used with deep wells, but a submersible pump is usually a better option for deep wells. Sizing water pumps and pressure tanks is routine for some plumbers and foreign to others. This chapter is going to give you plenty of data to use when working with pump systems.

The illustrations I have to offer you in this chapter are detailed and self­explanatory. I believe that you will be able to use this chapter as a quick-ref­erence guide to most of your pump questions. Look over the following illus­trations and you will find data on jet pumps, submersible pumps, and pressure tanks. The data will prove very helpful if you become involved with the in­stallation, sizing, or repair of water pumps (Figs. 8.1 to 8.37).

135

This check list is intended to bdp in making reliable submersible pump installations. Other data for specific pumps may be needed.

 

1. Motor Inspection

___ Л. Verify thai lire model. HP or KW. voltage, phase

and heitz on the motor nameplate match the installation requirements. Consider any special comision resistance required.

___ B, Check that I he motor lead assembly ts tight in Uie

motor and that the motor and lead are not damaged.

___ C. Test insulation resistance using a 500 or l(MX) volt

DC inegohmmeier, from each lead wire to the motor frame, Resistance should be at least 20 megohms, motor only, no cable.

D. Keep a record of motor model number, HP or KW, voltage, date code and serial number,

2. Pump Inspection

___ A. Check that the pump rating matches the motor, and

that it is not damaged.

___ B. Verily that the pump shaft turns freely.

3. Pump/Motor Assembly

___ A. If not yet assembled, check that pump and motor

mounting faces are free from dirt and uneven paint

thickness.

___ B, Assemble the pump and motor together so their

mourning faces are in contact, then tighten assembly holis or nuts evenly to manufacturer specifications.

И it is visible, chuck dial the pump shaft is raised slightly by assembly to the motor, conlilining impeller running clearance.

___ C. If accessible, check that the pump shaft rums freely.

___ D. Assemble the pump lead guard over the motor

leads. Do not eui nr pinch lead wire during assembly or handling of the pump during installation.

4. Power Supply and Controls

__ A. Verify that the power supply voltage, here?., and

KVA capacity malch motor requirements.

B, Use a matching control box with each single phase three wire motor.

___ C. Check that the electrical installation arid controls

meet all safety regulations and match the motor requirements, including fuse or circuit breaker size and motor overload protection. Connect all metal plumbing and electrical enclosures to (he power supply ground in prevent shock hazard, Comply with National and local codes.

5. Lightning and Surge Protection

___ A. Use properly rated surge (lightning) arresiors on all

submersible pump installations unless the installa­tion is operated directly from an individual gen­erator and/or is not exposed to surges. Motors 5HP and smaller which are marked “Equipped with Lightning Arrestors’contain internal arrestors.

 

B. Ciround all above ground arrestors with copper wire directly to the motor frame. or to metal drop pipe or casing which reaches below the well pumping level, Connecting to a ground rod does not provide good surge protection.

 

6. Electrical Cable

___ A. Use cable suitable for use in water, sized to carry’ the

motor current without overheating in water and in air, and complying with local regulations. To maintain adequate voltage at die motor, use lengths no longer than specified in die motor manufacturer s cable charts,

___ B. Include a ground wire to liie pump if required by

codes or. surge protection, connected lo the power supply ground Always ground any pump operated outside a drilled well.

7. Well Conditions

___ A, For adequate cooling, motors must have at least the

water flow shown on ils nameplate. If well conditions and construction do not assure this much water How will always come from below the motor, use a flow’ sleeve as shown in the Application, Installation & Maintenance Manual

___ B. If water temperature exceeds JO degrees C <86 T).

reduce live motor loading or increase the How rate to prevent overheating, as specified in the Application. Installation & Maintenance Manual.

B. Pump/Motor Installation

___ A. Splice motor leads lo supply cable using electrical

grade solder or compression connectors, and carefully insulate each splice with watertight tape or adhesive-lined shrink tubing, as shown in motor or pump installation data.

___ B. Support the cable to the delivery pipe every 10 feel

(3 meters) with straps or tape strong enough to prevent sagging. Use pads between cable and any metal straps.

___ C. A check valve in the delivery pipe is recommended,

even though a pump may be reliable without one. More than one check valve may be required, depending cm valve rating and pump setting. Install the lowest check valve below the lowest pumping level of the well, lo avoid hydraulic shocks which may damage pipes, valve or motor.

___ D. Assemble all pipe joints as lightly as practical, to

prevent unscrewing from motor torque. Recommended torque is at least 10 pound feet per HP (2 mcter-KG per KWi.

___ E. Set the pump fur enough below the lowest pumping

level to аччигс the pump inlet will always have at least the Net Positive Suction 1 lead |NPSI l) specified by the pump manufacturer, but at least 11) leet (3 meters) from the bottom of the well lo allow for sediment build up.

 

___ F. Cheek, insulation resistance from dry motor cable

ends to ground as the pump is installed, using а 5Ш or KM) volt DC megohm meter. Resistance may drop gradually as mere cable enters the water, but any sudden drop indicates possible cable, splice or motor lead damage. Resistance should meet motor manufacturer data,

9. After Installation

___ A. Check all electrical and waterline connections and

parts before starting the pump, Make sure water delivery will not wd any electrical parts, and recheck that overload protection in three phase controls meets requirements.

___ B. Strut the pump and check motor amps and pump

delivery. If normal, continue to run the pump until delivery is clear. If three phase pump delivery is low, it may be running backward because phase, sequence is reversed. Rotation may be reversed (with power off) by interchanging any two motor lead connections to the power supply.

___ C. Connect three phase motors for current balance

within 5% of average, using motor manufacturer instructions. Unbalance over 5c7c will cause higher motor temperatures and may cause overload trip, vibration, and reduced life.

___ D. Make sure that starling, running and stopping cause

no significant vibration or hydraulic shocks.

___ E. A Iter at least 15 minutes running, verify that pump

output, electrical input, pumping level, and other characteristics arc stable and as specified.

Date____________________ Filled In By

10. Installation Data

Well Identification_________________________________ _________________________________________

Check By ____________________________________ _

Date___ /____ (_____

Notes __________________________________________

 

KM A No.

 

REMAINING TABLES
REMAINING TABLES

Pump Inlet Setting___

Flow Sleeve: No

 

_ Yes. Dia.

 

Casing Depth______ Jt

□ Well Screen □ Perforated Casing From__ to_________ ft. &__ to________ ft-

 

— Well Depth_

Form No. 2207 2AM

 

REMAINING TABLES

Average water requirements for general

service around the home and farm

Each person per day, for all purposes

75 gal.

Each horse, dry cow, or beef animal

12 gal.

Each milking cow

35 gal.

Each hog per day

4 gal.

Each sheep per day

2 gal.

Each 100 chickens per day

4 gal.

Average amount of water required by

various home and yard fixtures

Drinking fountain, continuously flowing

50 to 100 gal. per day

Each shower bath

Up to 30 gal. @ 3-5 gpm

To fill bathtub

30 gal.

To flush toilet

6 gal.

To fill lavatory

2 gal.

To sprinkle V4" of water on each 1000

square feet of lawn

1б0 gal.

Dishwashing machine — per load

7 gal. @ 4 gpm

Automatic washer —per load

Up to 50 gal. @ 4-6 gpm

Regeneration of domestic water softener

50-100 gal.

Average flow rate requirements by

various fixtures

(gpm = gal. per minute; gph =

gal. per hour)

Shower

3-5 gpm

Bathtub

3-5 gpm

Toilet

3 gpm

Lavatory

3 gpm

Kitchen sink

2-3 gpm

У2” hose and nozzle

200 gph

1/4" hose and nozzle

300 gph

Lawn sprinkler

120 gph

FIGURE 8.3 ■ Average water requirements for general service. (Courtesy of McGraw-Hill)

Each horse

Approx. Gallons Per Day

12

Each producing cow

15

Each nonproducing cow

12

Each producing cow with drinking cups

30-40

Each nonproducing cow with drinking cups

20

Each hog

4

Each sheep

2

Each 100 chickens

4-10

Yard fixtures:

Vi-inch hose with nozzle

200

M-inch hose with nozzle

300

Bath houses

10

Camp

Construction, semipermanent

50

Day (with no meals served)

15

Luxury

100-150

Resorts (day and night, with limited plumbing)

50

Tourists with central bath and toilet facilities

35

Cottages with seasonal occupancy

50

Courts, tourists with individual bath units

50

Clubs

Country (per resident member)

100

Country (per nonresident member present)

25

FIGURE 8.4 ■ Daily water requirements. (Courtesy of McGraw-Hill)

Dwellings

Luxury

Multiple family, apartments (per resident)

Rooming houses (per resident)

Single family Estates _

Factories (gallons/person/shift)

Institutions other than hospitals Hospitals (per bed)

Laundries, self-serviced (gallons per washing, i. e., per customer)

Motels

With bath and toilet (per bed space)

Parks

Overnight with flush toilets Trailers with individual bath units Picnic

With bath houses, showers, and flush toilets With only toilet facilities (gal./picnicker) Restaurants with toilet facilities (per patron)

Without toilet facilities (per patron)

With bars and cocktail lounge (additional quantity) Schools Boarding

Day with cafeteria, gymnasiums and showers Day with cafeteria but no gymnasiums or showers Service stations (per vehicle)

Stores (per toilet room)

Swimming pools Theaters

Drive-in (per car space)

Movie (per auditorium seat)

Workers

Construction (semipermanent)

Day (school or offices per shift)

 

75

60

50

75

100-150

15-35

75-125

250-400

50

100

25

50

20

10

10

3

2

50-70

25

20

10

400

10

5

5

50

15

 

Providing an adequate water supply provides for a healthy family and higher production from livestock. Assuming the total daily requirement is calculated to be 1200 gpd (gallons per day), a pump would be selected for a capacity of 10 gpm (gallons per minute) based on the following formula:

 

1200 gph t 2 equals 600 gph (gal. per hr.)

 

REMAINING TABLES

FIGURE 8.4 ■ (Continued) Daily water requirements. (Courtesy of McGraw-Hill)

 

REMAINING TABLES

Engineering Data
Drop Cable Selection Chart

Single-phase, two or three-wire cable, 60 Hz (service entrance to motor)

 

REMAINING TABLES
REMAINING TABLES

REMAINING TABLES

Engineering data

Formulas and conversion factors
Centrifugal pumps

 

REMAINING TABLES

К

El

d

 

Volume

1 U. S, gallon — 231 cu. in,

1 U. S. gallon =■ 3-785 liters 1 Imperial gallon *1.2 U. S.

gallons

1 barrel (oil) я 42 U. S, gallons 1 cubic foot * 7.48 U. S, gallons

1 acre foot = 325,850 U. S.

gallons

1 cubic meter * 264,2 U. S.

gallons

Weight

1 U. S. gallon water weighs 8,35 lbs.

1 cubic foot water weighs

 

Head

1 lb. per sq. in. = 2.31 ft. of water 1 foot of water = 0-433 lbs. per sq. in. 1 inch of mercury = 1,133 ft. of water 1 atmosphere (sea level) — 14.7 lbs, per sq. in.

1 kilogram per sq. centimeter * 14,22 lbs. per sq. in.

Length

1 meter » 3.28 feet — 39.37 inches Power

1 horsepower = 745-7 watts 1 kilowatt * 1000 watts 1 kilowatt = 1.341 HP 100 boiler HP requires 7 gpm feed water approximately.

 

FIGURE 8.6 ■ Formulas and conversion factors for centrifugal pumps. (Courtesy of McGraw-Hill)

 

REMAINING TABLES

REMAINING TABLES

system

 

REMAINING TABLES

xtsll~x~trol

 

REMAINING TABLES

system

 

REMAINING TABLES

Relief valve

 

REMAINING TABLES

Submersible pump

 

REMAINING TABLES

REMAINING TABLES

FIGURE 8.7 ■ Pressure tank in use with a submersible pump. (Courtesy of McGraw-Hill)

REMAINING TABLES

О 1 2 3 456789 10 11 12

U. S. gallons per minute

FIGURE 8.8 ■ Performance rating chart for pump with 5 gallon-per- minute output. (Courtesy of McGraw-Hill)

REMAINING TABLES

FIGURE 8.9 ■ Performance rating chart for pump with 10 gallon-per- minute output. (Courtesy of McGraw-Hill)

1000

 

REMAINING TABLES

800

 

700

 

400

 

200

 

100

 

U. S. gallons per minute

 

FIGURE 8.10 ■ Performance rating chart for pump with 13 gallon-per — minute output. (Courtesy of McGraw-Hill)

REMAINING TABLES

 

REMAINING TABLES

REMAINING TABLES

REMAINING TABLES

800

 

700

 

400

 

200

 

100

 

U. S. gallons per minute

 

REMAINING TABLES

REMAINING TABLES

FIGURE 8.12 ■ Performance rating chart for pump with 25 gallon-per — minute output. (Courtesy of McGraw-Hill)

Output In gallons per hour

Discharge pressure 0 P. S.I.

 

REMAINING TABLES

Impeller

Pres, switch

Suction

Discharge

Shipping

Model no.

HP

Volts

material

setting

pipe size

size

weight

8130

Уз

115

Plastic

20-40

1У4”

■1/4"

46 lbs.

8131

Уз

115

Brass

20-40

1У4"

48 lbs.

8150

y2

115/230

Plastic

20-40

1У4”

‘■’A"

48 lbs.

8151

y2

115/230

Brass

20-40

1У4"

50 lbs.

8170

3/4

115/230

Plastic

30-50

IV*’

%"

50 lbs.

8171

3/4

115/230

Brass

30-50

1У4"

%"

52 lbs.

8110

1

115/230

Plastic

30-50

1У4”

52 lbs.

8111

1

115/230

Brass

30-50

1У4"

53 lbs.

FIGURE 8.14 ■ Performance ratings for jet pumps. (Courtesy of McGraw-Hill)

Подпись: PLUMBER'S AND PIPE FITTER'S CALCULATIONS MANUAL
Подпись: Impeller Pres, switch Suction Twin type Shipping Model Model HP Volts material setting pipe size drop pipe weight 1550 1050 Vz 115/230 Brass 30-50 1%" 1" x l'A” 65 lbs. 1575 1075 3/4 115/230 Brass 30-50 1У4" 1" X ІУ4" 71 lbs. 1575SW 1075SW % 115/230 Brass 30-50 1У." Г x 1УТ 66 lbs. 1510 1010 1 115/230 Brass 30-50 1У4" Г x l'A" 74 lbs. 1510SW 1010SW 1 115/230 Brass 30-50 1У4" 1" x I'A” 67 lbs. 1515SW 1015SW l‘/2 115/230 Brass 30-50 1У4” Г X l'A" 72 lbs.

FIGURE 8.15 ■ Performance ratings for multi-stage pumps. [Courtesy of McGraw-Hill)

REMAINING TABLES

FIGURE 8.16 ■ Shallow-well performance chart. (Courtesy of McGraw-Hill)

REMAINING TABLES

FIGURE 8.17 ■ A typical jet-pump set-up. (Courtesy of McGraw-Hill)

REMAINING TABLES

system

 

REMAINING TABLES

Pump

 

REMAINING TABLES

Dram

 

REMAINING TABLES
REMAINING TABLES

REMAINING TABLES

REMAINING TABLES

FIGURE 8.18 ■ A jet pump mounted on a pressure tank with a pump bracket. (Courtesy of McGraw-Hill)

REMAINING TABLES

FIGURE 8.19 ■ A typical piping arrangement for a jet pump. (Courtesy of McGraw-Hill)

REMAINING TABLES

FIGURE 8.20 ■ Bracket-mounted jet pump on a horizontal pressure tank. (Courtesy of McGraw-Hill)

REMAINING TABLES

FIGURE 8.21 ■ Small, vertical pressure tank installed above pump. (Courtesy of McGraw-Hill)

REMAINING TABLES

FIGURE 8.22 ■ Small, vertical pressure tank installed above pump. (Courtesy of McGraw-Hill)

REMAINING TABLES

REMAINING TABLESFIGURE 8.24 ■ An underground installation of a pressure tank. (Courtesy of McGraw-Hill)

REMAINING TABLES

REMAINING TABLES

FIGURE 8.25 ■ In-line pressure tank. (Courtesy of McGraw-Hill)

 

Stand models

 

REMAINING TABLES

FIGURE 8.26 ■ Stand-type pressure tank. (Courtesy of McGraw-Hill)

 

REMAINING TABLES

REMAINING TABLES

Model

Dimensions

Total

1,5/3,0 bar

2,0/3,5 bar

2,5/4,0 bar

System

Precharge

Shipping

No.

Diameter

Height

Volume

Drawdown

Connection

Pressure

Wt./Vol.

mm

mm

Ltr

Liter

Liter

Liter

FT

bar

KG/m3

WX 2,6

156

228

2.6

1,0

0,9

0,8

3/4

1,5

1,0/,005

WX4

156

302

4,1

1,5

1,4

1,2

3/4

1.5

1,5/,007

WX8

200

320

8

3,0

2.6

2,4

3/4

1,5

2,3/,02

WX 18

280

380

18

6,7

6,0

5,4

3/4

1,5.

4,1 / ,03

WX33

280

630

33

12,4

10,9

9,9

3/4

1,5

6,8 / ,05

 

REMAINING TABLES

FIGURE 8.27 ■ Specifications for in-line pressure tanks. (Courtesy of McGraw-Hill)

Подпись: WATER PUMPS ■ 157

10 bar series

 

REMAINING TABLES

Mode

 

WL 1855

 

560

 

805

 

REMAINING TABLES

801

 

REMAINING TABLES

560

 

805

 

180

 

560

 

1240

 

560

 

1700

 

300

 

750

 

1880

 

600

 

750

 

2340

 

800

 

1000

 

1960

 

1000

 

000

 

2740

 

600

 

2493

 

1200

 

2000

 

16 bar series

 

REMAINING TABLES

560

 

805

 

560

 

1240

 

560

 

1700

 

300

 

750

 

1880

 

600

 

750

 

2340

 

800

 

1801-20001

 

1960

 

1000

 

1000

 

2740

 

1600

 

REMAINING TABLES

2000

 

2493

 

REMAINING TABLES

REMAINING TABLES

1,5/3,0 bar

2,0/3,5 bar

2,5/4,0 bar

System

Connection

Precharge

Pressure

Shipping

Wt./Vol.

Liter

Drawdown

Liter

Liter

FT

bar

KG /m3

30

27

24

2

3,5

59 / ,25

68

60

54

2

3,5

83 / ,39

113

99

90

2

3,5

155/,53

225

198

180

2

3,5

285/1,06

300

264

240

2

3,5

360/1,32

375

330

300

3

3,5

400 /1,96

600

528

480

3

3,5

540/2,74

750

660

600

3

3,5

780 / 3,59

30

27

24

2

3,5

59/,25

68

60

54

2

3,5

83 / ,39

113

99

90

2

3.5

155/,53

225

198

180

2

3,5

285 /1,06

300

264

240

2

3,5

360 /1,32

375

330

300

3

3,5

400 /1,96

600

528

480

3

3.5

540/2,74

750

660

600

3

3,5

7890/3,59

30

27

24

2

3,5

64 / ,25

68

60

54

2

3,5

102/,39

113

99

90

2

3,5

220 / ,53

225

198

180

2

3,5

400/1,06

300

264

240

2

3,5

505/1,32

375

330

300

3

3,5

560 / 1,96

600

528

480

3

3,5

756/2,74

750

660

600

3

3,5

1330/3,5

FIGURE 8.28 ■ (Continued) Specifications for pressure tanks with replaceable bladder designs. (Courtesy of McGraw-Hill)

REMAINING TABLES

FIGURE 8.29 ■ Detail for a tank-tee set-up. (Courtesy of McGraw-Hill)

 

Dimensions

Total

Max.

Drawdown

ShipplRQ

Model

Diameter

Height

Volume

Accept.

2W40

30/50

40/50

m (Vo i. >

No.

(ini)

(in)

(tali)

Factor

(gala)

(gall)

(gala)

H>i feu 44>

WX-103-PS

12 V2

11 VA

8.6

028

3 1

2.7

22

20(2.4}

WX 200-PS

17 W

15 *8

140

0.31

5.2

43

38

29(4 0)

Precharge Pressure is 30 PSIG and Sys. Conn, is *4“ NPTM Filling lor 103-PS and i" NPTF Coupling lor 2Q0-PS. Maximum Working Pressure is 100 PSIG and Maximum Working Temperalure is 200" F.

 

FIGURE 8.30 ■ Pump-stand type of pressure tank. (Courtesy of McGraw — Hill)

 

REMAINING TABLES

REMAINING TABLESREMAINING TABLES

REMAINING TABLES

FIGURE 8.31 ■ Underground pressure tank specifications. (Courtesy of McGraw-Hill)

REMAINING TABLES

When the pump starts, water enters the WELL-X-TROL as system pressure passes the minimum pressure precharge. Only usable water is stored.

 

WELL-X-TROL has a sealed-in air chamber that is pre-pfessurized before it leaves our factory. Air and water do not mix eliminating any chance of “waterlogging” through loss of air to system

 

REMAINING TABLES

When water is demanded, pressure in the air chamber forces water into the system. Since WELL-X-TROL does not waterlog and consistently delivers the maximum usable water, minimum pump starts are assured.

 

FIGURE 8.32 ■ How diaphragm pressure tanks work. (Courtesy of McGraw-Hill)

 

Maximum starts per 24 hr. day

Motor rating

Single phase

Three phase

Up to 3A hp

300

300

1 hp thru 5 hp

100

300

7 У2 hp thru 30 hp

50

100

40 hp and over

100

 

FIGURE 8.33 ■ Recommended maximum number of times a pump should start in a 24-hour period. (Courtesy of McGraw-Hill)

 

REMAINING TABLES

O’*

ы

 

Подпись: PLUMBER’S AND PIPE FITTER’S CALCULATIONS MANUAL

Operating pressure—psig

discharge 20/40 30/50 40/60

rate gpm (approx.) 2.5

ESP I

ESP II

ESP I

ESP II

ESP I

ESP II

WX-104

WX-201

WX-104

WX-202

WX-104

WX-202

5

WX-201

WX-205

WX-202

WX-205

WX-202

WX-250

7

WX-202

WX-250

WX-203

WX-251

WX-205

WX-251

10

WX-203

WX-251

WX-205

WX-302

WX-250

WX-302

12

WX-205

WX-302

WX-250

WX-302

WX-251

WX-350

15

WX-250

WX-302

WX-251

WX-350

WX-251

WX-350

20

WX-251

WX-350

WX-302

(2JWX-251

WX-302

(2)WX-302

25

WX-302

(2JWX-302

WX-302

(2)WX-302

WX-350

(3)WX-251

30

WX-302

(2)WX-302

WX-350

(DWX-302

WX-350

(2)WX-350

35

WX-350

(DWX-302

WX-350

(DWX-350

(2)WX-350

(2JWX-251

(3)WS-302

40

WX-350

(DWX-350

(2)WX-350

(2)WX-251

(3)WX-302

(2)WX-302

(DWX-302

(2)WX-350

 

FIGURE 8.34 ■ Sizing and selection information for perssure tanks. (Courtesy of McGraw-Hill)

Updated: 17 ноября, 2015 — 7:51 пп