Category Framing

Protection from Decay

Moisture and warm air are catalysts of fungus, which causes dry rot that can destroy a building.

In addition to calling for ventilation to control moisture, the code also requires decay-resistant wood wherever moisture can come in contact with structural wood. Some areas of the country are more conducive to decay than others. The code requires naturally durable wood or preservative-treated wood in the following situations:

• Wood joist or the bottom of the wood floor structure if less than 18" from exposed ground. (See “Joists & Girder Protection" illustration.)

• Wood girders if closer than 12" from exposed ground.

• Wall plates, mudsills, or sheathing that rest on concrete or masonry exterior walls less than 8" from exposed ground. (See “Exterior Wall Decay Protection" illustration.)

• Sills or sleepers that rest on a concrete or masonry slab in direct contact with the ground, unless separated from the slab by an impervious moisture barrier. (See “Decay Protection from Slab" illustration later in this chapter.)

• The ends of wood girders entering exterior masonry or concrete walls having less than %" clearance on tops, sides, and ends. (See “Ends of Girders in Masonry or Concrete" illustration.)

• Posts or columns that support permanent structures and are themselves supported by a masonry concrete slab or footing in direct contact with the ground. (See “Post and Column Decay-Resistant Wood" illustration.)

Space on top, sides, and end must be V2" or girder needs to be of decay – resistant wood.

Nailing

Nailing is one of the most important parts of framing. Table 2304.9.1, Fastening Schedule (see IBC Nailing Table), is taken directly from the IBC 2009. The table shows use of alternate nails. The 3” x 0.131” nail is the most common nail gun nail used for framing.

TABLE 2304.9.1 FASTENING SCHEDULE

CONNECTION

FASTENINGam

LOCATION

1. Joist to sill or girder

3 – 8d common (2’/2 0.131 ) 3 – 3 0.131 nails 3 – 3 14 gage staples

toenail

2. Bridging to joist

2 – 8d common (2’/2 X 0.131 ) 2 – 3 0.131 nails 2 – 3 14 gage staples

toenail each end

3. 1 6 subfloor or less to each joist

2 – 8d common (2’/2 0.131 )

face nail

4. Wider than 1 6 subfloorto each joist

3 – 8d common (2’/2 0.131 )

face nail

5. 2 subfloor to joist or girder

2 – 16d common (3’/2 0.162 )

blind and face nail

6. Sole plate to joist or blocking

Sole plate to joist or blocking at braced

16d (3V2 0.135 ) at 16 o. c. 3 0.131 nails at 8 o. c.

3 14 gage staples at 12 o. c.

3 – 16d (3V2 0.135 ) at 16

typical face nail

wall panel

4 – 3 0.131 nails at 16 4 – 3 14 gage staples per 16

braced wall panels

7. Top plate to stud

2 – 16d common (3V2 0.162 )

3 – 3 0.131 nails 3 – 3 14 gage staples

end nail

8. Stud to sole plate

4 – 8d common (2’/2 0.131 )

4 – 3 0.131 nails 3 – 3 14 gage staples

2 – 16d common (3V2 0.162 )

3 – 3 0.131 nails 3 – 3 14 gage staples

toenail end nail

9. Double studs

16d (3V2 0.135 ) at 24 o. c. 3 0.131 nail at 8 o. c.

3 14 gage staple at 8 o. c.

face nail

10. Double top plates Double top plates

16d (3V2 0.135 ) at 16 o. c. 3 0.131 nail at 12 o. c.

3 14 gage staple at 12 o. c.

8-16d common (3V2 0.162 ) 12-3 0.131 nails 12-3 14 gage staples

typical face nail lap splice

11. Blocking between joists or rafters to top plate

3 – 8d common (2’/2 0.131 ) 3 – 3 0.131 nails 3 – 3 14 gage staples

toenail

12. Rim joist to top plate

8d (2V2 0.131 ) at 6 o. c. 3 0.131 nail at 6 o. c.

3 14 gage staple at 6 o. c.

toenail

13. Top plates, laps and intersections

2 – 16d common (3V2 0.162 )

3 – 3 0.131 nails 3 -3 14 gage staples

face nail

14. Continuous header, two pieces

16d common (3’/2 0.162 )

16 o. c. along edge

15. Ceiling joists to plate

3 – 8d common (2’/2 0.131 ) 5 – 3 0.131 nails 5 – 3 14 gage staples

toenail

16. Continuous header to stud

4 – 8d common (2’/2 0.131 )

toenail

(continued)

Source: The International Building Code, copyright © 2009, with permission from the International Code Council, Inc.

For SI: 1 inch = 25.4 mm.

a. Common or box nails are permitted to be used except where otherwise stated.

b. Nails spaced at 6 inches on center at edges, 12 inches at intermediate supports except 6 inches at supports where spans are 48 inches or more. For nailing of wood structural panel and particleboard diaphragms and shear walls, refer to Section 2305. Nails for wall sheathing are permitted to be common, box or casing.

c. Common or deformed shank (6d – 2 0.113 ; 8d – 2V2 0.131 ; 10d – 3 0.148 ).

d. Common (6d – 2 0.113 ; 8d – 2V2 0.131 ; 10d – 3 0.148 ).

e. Deformed shank (6d – 2 0.113 ; 8d – 2V2 0.131 ; 10d – 3 0.148 ).

f. Corrosion-resistant siding (6d – 17/8 0.106 ; 8d – 23/8 0.128 ) or casing (6d – 2 0.099 ; 8d – 2V2 0.113 ) nail.

g. Fasteners spaced 3 inches on center at exterior edges and 6 inches on center at intermediate supports, when used as structural sheathing. Spacing shall be 6 inches

on center on the edges and 12 inches on center at intermediate supports for nonstructural applications.

h. Corrosion-resistant roofing nails with 7/16 – inch-diameter head and 11/2-inch length for 1/2-inch sheathing and 1 3/4-inch length for 25/32-inch sheathing.

i. Corrosion-resistantstapleswithnominal7/16-inchcrownand 11/8-inchlengthfor 1/2-inchsheathingand 1 1/2-inchlengthfor25/32-inchsheathing. Panelsupportsat 16 inches (20 inches if strength axis in the long direction of the panel, unless otherwise marked).

j. Casing (1V2 0.080 ) or finish (1V2 0.072 ) nails spaced 6 inches on panel edges, 12 inches at intermediate supports.

k. Panel supports at 24 inches. Casing or finish nails spaced 6 inches on panel edges, 12 inches at intermediate supports.

l. For roof sheathing applications, 8d nails (2V2 0.113 ) are the minimum required for wood structural panels.

m. Staples shall have a minimum crown width of 7/16 inch.

n. For roof sheathing applications, fasteners spaced 4 inches on center at edges, 8 inches at intermediate supports.

o. Fasteners spaced 4 inches on center at edges, 8 inches at intermediate supports for subfloor and wall sheathing and 3 inches on center at edges, 6 inches at interme­diate supports for roof sheathing.

p. Fasteners spaced 4 inches on center at edges, 8 inches at intermediate supports.

Source: The International Building Code, copyright © 2009, with permission from the International Code Council, Inc.

Termite Protection

Framers in many areas of the country have to be concerned about protection against termites. Pressure preservative-treated wood, naturally termite-resistant wood, or physical barriers can be used to prevent termite damage. The following map shows termite infestation probability by region.

Termite Infestation Probability

Conclusion

An important part of your job as a lead framer is being aware of the building codes that apply to framing in your part of the country. You should be aware of how to use the code and of any revisions to those codes. Although locating information you need in the code books is often the hardest part of using the codes, the “Framing Index" at the beginning of this chapter should make this easier for you. It’s a good feeling to know that you have framed a building the way it’s specified according to code.

Stair & Ramp Framing

The width of stairs must be a minimum of 36” from finish to finish. Handrails may project into the 36” a maximum of 4%" on each side. (See “Stairs" illustration.)

Two sets of tread and riser dimensions apply to minimum and maximum requirement. One set is for Group R-3, Group R-2, and Group 4 (houses, apartments, dormitories, non-transient housing).

The other is for all other groups. The first set requires a maximum riser height of 7%" and a minimum
tread depth of 10”, while the second requires a maximum riser height of 7”, a minimum riser height of 4”, and a minimum tread depth of 11”.

The variation in riser height within any flight of stairs must not be more than 3/s” from finish tread to finish tread. The variation in tread depth within any flight of stairs cannot be more than 3/s” from the finish riser to the nose of the tread.

Headroom for stairways must have a minimum finish clearance of 6′-8”, measured vertically from a line connecting the edge of the nosings.

Handrails may not project more than 4.5 inches on either side. 44” minimum if occupant load is 5o or more. Large buildings: Minimum equals occupant load multiplied by.3 inches per occupant but total not less than 44".

The difference in the largest tread or riser cannot be more than 3/s" bigger than the smallest tread or riser. Stairs with solid risers are required to have tread nosing not less than %" or more than Ш"

Handrails for stairs must have a height of no less than 34" and no more than 38", measured vertically from a line created by joining the nosing on the treads.

Stairway landings must be provided for each stairway at the top and bottom. The width each way of the landing must not be less than the width of the stairway it serves. The landing’s minimum dimension in the direction of travel cannot be less than 36", but does not need to be greater than 48" for a stair having a straight run. (See “Stair Landing" illustration.)

Circular stairways should have a minimum tread depth at a point 12" from the edge of the tread at its narrowest point of not less than 11". According to both the IRC and the IBC, the minimum depth at any point must be 6". (See “Circular Stairs" illustration.)

Spiral stairways must have a minimum width of 26". Each tread must have a minimum tread width of 71/г" at a point 12" from the narrow edge

of the tread. The rise must be no more than 9%". All treads must be identical. The headroom is a minimum of 6′-6". (See “Spiral Stairs" illustration.)

The maximum slope on a ramp is 8%, or one unit of rise for 12 units of run. Some exceptions (where technically infeasible) are available for slope of 1 unit vertical in 8 units horizontal-12-%%. Handrails must be provided when the slope exceeds 8.33%, or one unit of rise and 12 units of run.

The minimum headroom on any part of a ramp is 6′-8".

A minimum 36" x 36" landing is required at the top and bottom of a ramp and where there is any door, or where the ramp changes direction. The actual minimum landing dimensions will depend on the building use and occupant capacity. This minimum does not apply to non-accessible housing.

The maximum total rise of any ramp cannot be more than 30" between level landings. (See “Ramps" illustration later in this chapter.)

If the building’s occupancy capacity is more than 50, then the minimum landing dimensions are 44".

The actual minimum landing dimensions will depend on the building use and occupant capacity.

Ventilation

Ventilation is required so that condensation does not occur on the structural wood, causing dry rot and the deterioration of the building. Cross ventilation is required in crawl spaces, attics, and in enclosed rafter spaces. In rafter spaces between the insulation and the roof sheathing, there must be at least 1" clear space.

The total area of the space to be ventilated cannot be more than 150 times the size of the area of the venting. (Both are measured in square feet.)

Ceiling Framing

Ceiling joists must have bearing support similar to that of rafters. The bearing must be Ш" on wood or metal, and not less than 3" on masonry or concrete.

The most important thing to remember about ceiling joists is that if they are used to tie the rafter­bearing walls at opposite ends of the building, then those joists must be securely attached to the walls, to the rafters, and to each other at the laps. If the ceiling joists do not run parallel with the rafters, an equivalent rafter tie must be installed to provide a continuous tie across the building.

The IRC calls for a minimum ceiling clearance of 7′. The IBC requires 7′-6" with the exception of bathrooms, kitchens, laundry, and storage rooms, where it can be 7′.

There are three exceptions to this rule. First, beams or girders can project 6" below the required ceiling height if they are spaced more than 4′ apart. The second exception is for basements without habitable spaces. These may have a minimum height of 6′-8" and may have beams, girders, ducts, and other obstructions at 6′-4" in height. The third exception is for a sloped ceiling. Fifty percent of the sloped ceiling room area can be less than the minimum ceiling height. However, any portion of the room less than 5′ in height cannot be included in figuring the room area. (See "Ceiling Heights" illustration later in this chapter.)

Truss Framing

Trusses are an engineered product. This means that an engineer or design professional must design them for each job to form a roof/ceiling system. Components and members of the trusses should not be notched, cut, drilled, spliced, or altered in any way without the approval of a registered design professional.

Wall Bracing

Wall bracing is needed to keep buildings from falling. Sheathing the exterior walls is a typical way to provide bracing. The architect, engineer, or whoever creates the plans will specify when any special bracing is needed. Although you don’t need to know everything about wall bracing, it is good to have a basic understanding of it.

Two common exceptions to these methods are:

(1) the short wall often used for garages, and

(2) the 24" wide corner wall. Note that cripple walls have their own requirements.

The IBC states that braced wall panels must be clearly indicated on the plans. However, this is not always the case in the real world. Although shear walls are usually marked on the plans, braced wall panels often are not.

The IBC and IRC contain a table that shows braced wall panel limitations and requirements.

The limitations are related to the seismic design category, and to how many stories are built on top of the walls.

Where braced wall lines rest on concrete or masonry foundations, they must have anchor bolts that are not less than W in diameter or a code-approved anchor strap. The anchor bolts or straps should be spaced not more than 6 apart (or not more than 4 apart if the building is over two stories).

Each piece of wall plate must contain at least two bolts or straps. There must be one between 4" and 12" from each end of each piece. A nut and washer must be tightened on each bolt. In IBC seismic design categories D, E, and F, engineered shear walls

Anchor Bolts

require 0.229” x 3" x 3" plate washers. In IRC seismic design categories D0, D^ D2, and E, braced walls require 0.229" x 3" x 3" plate washers. (See “Anchor Bolts" illustration.) These requirements also apply to townhouses in seismic design category C.

The eleven basic construction methods for braced wall panels are as follows:

1. LIB—Let-in-bracing

2. DWB—Diagonal wood boards

3. WSP—Wood structural panel

4. SFB—Structural fiberboard sheathing

5. GB—Gypsum board

6. PBS—Particleboard sheathing

7. PCP—Portland cement plaster

8. HPS—Hardboard panel siding

9. ABW—Alternate braced wall

10. PFH—Intermittent portal frame

11. PFG—Intermittent portal frame at garage

Rafter Framing

Ridge boards must be at least 1" nominal in width and must be as deep as the cut end of the rafter.

Hip and valley rafters must be at least 2" nominal and must be as deep as the cut ends of the rafters connecting to the hip of the valley. Gusset plates as a tie between rafters may be used to replace a ridge board.

Rafters must have a bearing surface similar to that of joists at their end supports. Bearing needs to be Ш" on wood or metal and not less than 3" on masonry or concrete.

Drilling and notching have the same limitations for rafters as they do for floor joists. (See “Rafter Drilling & Notching" illustration.)

To prevent rotation of rafter framing members, lateral support or blocking must be provided for rafters and ceiling joists larger than 2 x 10s.

Bridging must be provided for roofs or ceilings larger than 2 x 12. The bridging may be solid blocking, diagonal bridging, or a continuous 1" x 3" wood strip nailed across the ceiling joists or rafters at intervals not greater than 8′. Bridging is not needed if the ceiling joists or rafters are held in line for the entire length with, for example, sheathing on one side and gypsum board on the other.

When rafters are used to frame the roof, the walls that the rafters bear on must be tied together by a connection to keep them from being pushed out.

If these walls are not tied together, then the ridge board must be supported by or framed as a beam in order to support the ridge. Ceiling joists are typically used to tie the walls together. The ceiling joists must be tied to the rafters, the walls, and any lapping ceiling joists. (See ceiling joists.)

Wall Framing

Stud spacing should be shown on the plans, but it is still good to be familiar with the code limitations. For 2 x 4 studs less than 10 feet tall, the maximum stud spacing is 24" O. C., provided the wall is supporting one floor or a roof and ceiling only. For the support of one floor, a roof, and ceiling, 16" O. C. is the maximum. To support two floors, a roof, and a ceiling with a maximum spacing of 16" O. C. and height of 10′, a minimum of 3 x 4 studs must be used. If studs are 2 x 6, a wall can support one floor, a roof, and ceiling at 24" O. C., or two floors, a roof, and ceiling at 16" O. C. Again, this stud spacing only applies to walls that don’t exceed 101 in height. (See "Stud—Spacing and Size" illustration.)

Cripple walls less than 41 in height should be framed with studs at least as big as those used in the walls above them. If the cripple walls are higher than 41, then the studs need to be at least the size required for supporting an additional floor level (as described in previous paragraph). (See "Foundation Cripple Walls" illustration.)

Double plates are needed on top plates for bearing and exterior walls. The end joints of the top plates and double plates should be offset by at least 48”. The IRC allows a 24” offset at nonstructural interior walls. The end joints need to be nailed with at least eight 16d nails or twelve 3” x 0.131" nails on each side of the joint. A single top plate may be used if the plates are tied together at the joints, intersecting walls, and corners with 3” x 6” galvanized steel plates or the equivalent, and all rafters, joists, or trusses are centered over the studs. (See “Walls, Top and Double Plate" illustration.)

Allowable drilling and notching is different for bearing or exterior walls, and for non-bearing or interior walls. Bearing or exterior walls can be notched up to 25% of the width of the stud and drilled up to 40% of the stud provided that the hole is at least 5/8” away from the edge. With interior non-bearing walls, the percentages are 40% for notches and 60% for drilling. (See “Drilling & Notching Studs, Exterior & Bearing Walls" and “Drilling & Notching Studs, Interior Nonbearing Walls" illustrations later in this chapter.)

Header sizes for exterior and bearing walls should be specified on the plans. For nonbearing walls, a flat 2 x 4 may be used as a header for a maximum of up to 8′ span where the height above the header to the top plate is 24” or less. (See “Header for Nonbearing Walls" illustration later in this chapter.)

Fireblocking refers to material you install to prevent flames from traveling through concealed spaces between areas of a building.

The location of fireblocks is sometimes difficult to understand.

It helps to think of where flames would be able to go. A 1%”- thick piece of wood can create a fireblock. If you place a row of these blocks in a wall, you create
a deterrent for the vertical spread of fire. Vertical and horizontal fireblocks are required in walls at least every 10′. (See “Fireblocking Vertical" and “Fireblocking Horizontal" illustrations later in this chapter.)

In a “party wall" construction, where you have two walls next to each other, you can create a fireblock by installing a stud in the space between the studs in the two adjoining walls. This creates a vertical fireblock. Note that %” gypsum board can also be used to create this type of fireblock.

Fireblocking is required between walls, floors, ceilings, and roofs. Typically, the drywall covering creates this fireblock. If it doesn’t, then fireblocking is needed. Where fireblocking is required behind the ledger, it can be installed at the interconnections of any concealed vertical and horizontal space like that which occurs at soffits, drop ceilings, or cove ceilings. (See “Fireblocking at Interconnections" illustration later in this chapter.)

Stair stringers must be fireblocked at the top and bottom of each run and between studs along the stair stringers if the walls below the stairs are unfinished.

Bored holes cannot be bigger than 40% of stud width.

For 2 x 4 = i3/8" maximum For 2 x 6 = 23/i6 maximum

5/8" minimum between hole and edge of stud

Notch cannot be bigger than 25% of stud depth.

For 2 x 4 = 7/8" maximum For 2 x 6 = 13/8" maximum

With doubled studs, bored hole may be as big as 60% of stud width. No more than two successive studs should be doubled and bored up to 60%.

For 2 x 4 studs = 21/8"

For 2 x 6 studs = 35/i6"

Bored holes cannot be bigger than 60% of stud depth

For 2 x 4 = 2/8" maximum For 2 x 6 = 35/i6" maximum

5/8" minimum between hoi and edge of stud

Framing According to Code

Floor Framing

Following are the code requirements and instructions related to floor framing:

• Double joists are required under parallel bearing walls.

• If pipes penetrate floors where double joists are required, the joists must be separated and have full-depth, solid blocks at least every 4′ along their length.

• Bearing for joists must be Ш" minimum on wood or steel, and 3" minimum on concrete or masonry.

• Where joists lap, there must be a minimum lap of 3" or a wood or metal splice of equal strength.

• The ends of joists must be kept from turning by using Ш" full-depth solid blocking or by attaching them to a header, band, rim joist, or adjoining stud.

• Full-depth, solid blocking is required at intermediate supports in IRC seismic design categories D1, D2, and E. (See seismic maps in Chapter 9.)

• Bridging at 8′ O. C. is required only when joists are larger than 2 x 12, and both edges are not held in line, as with plywood floor sheathing and drywall sheathing, or if thicker than

2” nominal.

The “Floor Joists—Anchor or Ledger" illustration below shows how joists framing into girders must be supported by framing anchors or a 2 x 2 or larger ledger.

Engineered wood products, such as I-joists, can be notched according to the manufacturer’s specifications. (See Chapter 8 for more on engineered wood products.)

The “Framing Floor Openings" illustration shows the following code requirements and instructions
related to framing around openings in floors.

• If the header joists are more than 4′, the header joists and trimmer joists should be doubled.

• If the distance from the bearing point of a trimmer joist to the header joist is more than 3′, the trimmer joists should be doubled.

• If the header joist is greater than 6′, hangers must be used.

• If the tail joists are more than 12′, use framing anchors or a 2 x 2 ledger.

The “Seismic Floor Opening Framing" illustration shows what to do if you are building in IRC seismic design categories B, C, D, or E and the opening is greater than 4′ perpendicular to the joists. In such cases, you must provide blocking beyond the headers, and metal ties must be used to connect the headers with the blocks.

Floor Joists—Anchor or Ledger

Joist framed into girder must be supported by framing anchors or 2 x 2 or bigger ledger

Floor Joists—Drilling & Notching Requirements

/M<®n«aDtomsapf0lt

D

D/3 maxima

D

D/3 maximum

2" тіпіплип

D/ 6 maximum

D/6 racDciroura

i, Notching ^1

^NotPei®^

Trimmer joist

If header joist is more than 4′, double header joist and double trimmer joist.

Seismic Floor Opening Framing with an Opening Greater than 4′ Perpendicular to the Joists

or

Metal tie 16 ga. x iy2" x (opening width + 4′-0") (1 each side) use 24-16d common nails.

Sheathing to go on top of joists

From the IBC Code; this information is not listed in the IRC.

BUILDING CODE REQUIREMENTS

Framers, builders, architects, engineers, and building inspectors alike have contributed to the system of building codes we use today. You should be aware of the codes that apply to the part of the country you are working in, as well as the important features of those codes. This chapter will discuss what you should know about building code requirements.

Introduction to Building Codes

The Evolution of Building Codes

Although carpentry is one of the oldest professions, framing as we know it today didn’t start until 1832 when a man named George Snow wanted to build a warehouse in Chicago. It was difficult to obtain enough large timbers to build the structure using the traditional post and beam method. Being creative (as all good builders and lead framers must be), he cut up the small timbers he had growing on his property into pieces similar to 2 x 4s. He placed them in a repetitive manner, thus creating the first 2 x 4 style walls.

Since then, architects, engineers, builders, building inspectors, and framers have all contributed to the system we use today. Along the way, builders constructed buildings in the way they saw fit. Although this “every man for himself" approach to building gave us structures to live and work in, it did not guarantee that such buildings would last a lifetime, be safe to live and work in, or stand up against earthquakes and hurricanes.

It wasn’t until 1915 that a group of building officials decided they needed a standard. That year, the Building Officials & Code Administrators International (BOCA) was established to bring some uniformity to the systems being used.

The IBC

Two other building code agencies appeared not long after: the International Conference of Building Officials (ICBO), and the Southern Building Code Congress International (SBCCI). All three organizations worked to meet the particular needs of their regions of the country.

In the year 2000, these agencies combined their codes to create one common code that would cover the entire country. This code is divided into two books: the International Residential Code (IRC), which covers all one – and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories in height, and the International Building Code (IBC), which covers all buildings. Separating the code in this way makes it easier to find the information you need. If you are building only houses, duplexes, or townhouses, you would go straight to the IRC.

There are two ways to comply with the code. The prescriptive method, most commonly used, gives specific requirements (such as how many inches on center to space the framing lumber) to build walls that are acceptable. The performance method tells us how a person can determine the strength of a wall using properly stamped, graded lumber, and if that strength meets the minimum code requirements.

Because the prescriptive system is most commonly used, it is the one we’ll cover here. It applies to conventional construction otherwise known as platform or balloon framing, which has been developed over the years on job sites, and has been tested and standardized. Prescriptive code requires no “engineering" design by a registered professional, as long as the project is built in compliance with the International Residential Code (IRC) or International Building Code (IBC).

(Note that with a performance-rated system, you will have a set of plans that you must follow to the letter. These plans come with structural components that must be used exclusively with the plans. Performance-rated codes require design by a registered professional who must specify in accordance with the IRC or IBC.)

A Framer’s Code Responsibility

Although it may seem that the codes are written for lawyers instead of framers, framers must be sure that their work complies to code. Note that some areas of the country may not be covered by a statewide, town, city, or county code. (Counties have historically been the jurisdictions controlling code establishment and enforcement.) Note, too, that code-writing organizations are not government agencies, so codes are not enforceable until or unless a government jurisdiction accepts the codes and makes them part of local law.

Code Revisions & Time Delays

Code Revisions

Revisions are important to keep in mind when working with codes. Codes are normally updated annually, and revised versions are published every three years. Typically, the revisions are not major, but it is important to know which code you must comply with. On some jobs the plans will indicate which codes apply. This information can usually be found on the cover page or with the general specifications in the plans. If the applicable code is not shown on the plans, ask the builder, owner, or whoever acquired the building permit about the code.

Time Delays

Another thing to keep in mind is the time that may elapse between when the code-writing organizations publish a revised code and when that code edition becomes the ruling code on the job you are framing. There are delays between when the code agencies certify the new codes and when the local government agencies review and approve them. There can also be delays between the date the permit is issued and the date the job is framed. It is not unusual to be working on plans that are three or four years or more behind the current building code. Although you have to comply with the code that is specified on the plans or that was used when the building permit was approved, you should also understand the current code because, in general, additions to the codes are improvements, or ways that contribute to making a building stronger. After every major earthquake or hurricane, codes have been adjusted and upgraded. By using the latest code, you can feel confident that you are framing with the latest construction knowledge.

Latest Code Used in This Book

This book uses the 2009 edition of the IBC and IRC to explain the major features of codes related to framing. These include structural requirements and life safety issues, and the spreading of fire. Although the code books may seem big and intimidating when you first see them, the number of pages that deal with framing are relatively few.

The following IBC & IRC Framing Index table is a handy list of all the framing sections of either code you might need. It was compiled based on the 2009 code books. In the IRC, the framing information can be found primarily in 4 of the total 43 chapters. In the IBC, 3 of the total 35 chapters deal with framing. The IRC framing chapters are 3, 5, 6, and 8. The IBC chapters containing framing information are 10, 12, and 23.

Important Code Features

What follows are key features of the code, and illustrations presented in a framer-friendly way. If you do a lot of framing, it’s a good idea to have a copy of the code book available for reference.

The three major categories used in the IBC are:

• Use and occupancy classification

• Fire-resistance-rated construction classification

• Seismic design categories

In the IBC, the seismic design categories are based on their seismic use group. The categories are A, B, C, D, Da, E, and F. Although they are similar to the categories in the IRC, there are some differences.

Framing code

IRC #

IRC

page

IBC #

IBC

page

Table-Fig.

Floor Framing

Double joists under bearing partitions

R502.4

114

2308.8.4

478

Bearing

R502.6

114

2308.8.1

478

Girders

2308.7

478

Minimum lap

R502.6.1

114

2308.8.2

478

Joist support

R502.6.2

114

2308.8.2

478

Lateral support

R502.7

114

2308.8.2

478

Bridging

R502.7.1

114

2308.8.5

483

Drilling and notching

R502.8

114

2308.8.2

478

Framing around openings

R502.10

114

2308.8.3

478

Framing around openings – seismic

2308.11.3.3

513

Wall Framing

Stud size, height and spacing

R602.3

146

2308.9.1

483

R602.3.1

IBC-2308.9.1

Cripple wall stud size

R602.9

157

2308.9.4

489

Cripple wall connection

2308.11.3.2

513

IBC-2308.11.3.2

Double and top plate overlap

R602.3.2

146

2308.9.2.1

483

Drilling and notching

R602.6

155

2308.9.10

489

R602.6(1)&(2)

2308.9.11

489

R602.6.1

Headers

R602.7

157

R502.5(1)&(2)

R602.7.2

2308.9.5

489

IBC-2308.9.5&6

Fireblocking

R602.8

157

717.2

121

Wall bracing

R602.10&11

159-185

R602.10.2-

R602.11.2

2308.9.3

484-489

IBC-2308.9.3&(1)

Braced wall lines

2308.3

477

Anchor bolts

R602.11.1

184

2308.3.3

477

R602.3(2)

2308.6

478

Plate washers

R602.11.1

184

2308.12.8

516

Rafter Framing

Ridge board and hip & valley rafters

R802.3

374

2308.10.4

493

Rafter bearing

R802.6

374

Drilling and notching

R802.7

375

2308.10.4.2

511

Lateral support

R802.8

375

2308.10.6

511

Framing around openings

R802.9

375

2308.10.4.3

511

Roof tiedowns & wind uplift

R802.11

376

2308.10.1

489

Rafter connections

R802.3.1

374

2308.10.4.1

493

Ceiling Framing

Ceiling heights

R305.1

54

1208.1

273

Ceiling joist lapped

R802.3.2

374

Ceiling joists bearing

R802.6

374

Ceiling joist connectors

2308.10.4.1

493

Ceiling framing

2308.1

489

IBC-2308.10.2(1)&(2)

Compiled by the author from the International Residential Code, copyright © 2009. The 2009 International Residential Code is a copyrighted work of the International Code Council.

Truss Framing

Truss bracing

R802.10.3

376

2303.4.1.2

455

Truss alterations

R802.10.4

376

2303.4.5

455

Attic Access

Attic spaces

R807.1

431

1209.2

274

Attic access

R807.1

431

1209.2

274

Stair & Ramp Framing

Stair landings

R311.7.5

60

1009.5

231

Stair width

R311.7.1

60

1009.1

230

Stair treads & risers

R311.7.4

60

1009.4

230

Stair headroom

R311.7.2

60

1009.2

230

Spiral stairs

R311.7.9.1

61

1009.9

232

Curved stairs

1009.8

232

Handrails

R311.7.7

60

1009.12

233

Ramps

R311.8

61

sect. 1010

233

Ventilation

Attic

R806

430-431

1203.2

271

Under floor

R408

108

1202.3

271

Roof

R806

430

1503.5

288

Nailing

Nailing

R602.3(1)

147

2304.9.1

462

IBC-2304.9.1

Sheathing nailing

R602.3(1)

148

2304.9.2

464

IBC-2304.9.1

Prevention of Decay

Pressure treated

R317

65

2304.11.1

465

Pressure treated joists, girders & subfloor

2304.11.2.1

465

Pressure treated framing

2304.11.2.3

465

Pressure treated sleepers & sills

2304.11.2.4

465

Girder ends at masonry

2304.11.2.5

465

Pressure treated post & columns

R317.1.4

65

2304.11.2.7

465

2304.11.4.1

465

Pressure treated laminated timbers

2304.11.3

465

Pressure treated wood contact with ground

2304.11.4

465

Pressure treated wood structural members

R317.1.5

65

2304.11.4.2

466

2304.11.5

466

Termite protection

termite protection

R318

66

2304.11.6

466

termite probability map

40

R301.2(6)

Miscellaneous

Wind limitations

R301.2.1

23

Seismic limitations

R301.2.2

44

Minimum fixture clearance bath & shower

R307

55

R307.1

Framing around flues & chimneys

2304.5

456

SIPs (Structural Insulated Panel) Walls

R613

348-356

Safety

Safety

33

567

Safeguards

33

567

Compiled by the author from the International Residential Code, copyright © 2009. The 2009 International Residential Code is a copyrighted work of the International Code Council.

Positive Placement Nail Guns

Earthquakes, hurricanes, and tornados continue to wreak havoc on our wood frame houses and buildings. We will never be able to completely protect against the worst case scenario, however our codes are continually improving so that we can make our buildings stronger. A big part of this improvement has been the addition of connection hardware. Whereas most connections used to be secured by nails, connections needed to establish shear and diaphragm strength are now secured by hardware. Most of this hardware is fastened with nails and in many cases a large number of nails. For example, where a small framing clip may take 12 nails, a four foot strap may take 32 nails, depending on the particular size and type of connector.

Because of all the additional hardware nailing, nail gun manufacturers have come out with positive placement nail guns that are specially made for nailing on hardware. There are different styles but they all use the same nails which are different
from standard nail guns. The nails are hardened and come in four sizes which are.131 X 1-1/2",

.148 1-1/2", .148 X 2-1/2", and.162 : 2-1/2". The guns use two methods to find the nail holes in the hardware. One style uses a probe that is placed in the hole, and then the gun directs the nail. In the other style, the nail protrudes so that the nail is placed in the hardware hole before firing the gun.

You need to make sure you use the right nail for the hardware. Each piece of hardware has its own nail requirements. If you use too big a nail you can fracture the steel around the nail hole, and if you use too small a nail you will not develop the appropriate strength needed. Hardware manufacturer specifications note the requirements. For example on the web at strongtie. com, Simpson Strong-Tie Company lists all their hardware with the amount and size of nails needed. There is also a convenient nail replacement chart which lists some nail size substitutions. This is helpful when you are installing hardware that was designed for standard nails but you are using positive placement gun nails. You can find this chart at strongtie. com/ products/connectors/nails. asp.

Conclusion

Quality of installation is probably the most important part of framing to withstand the forces of nature. APA (formerly the American Plywood Association, now the Engineered Wood Association) confirmed this fact when it conducted a study of the construction failures in the aftermath of Hurricane Andrew. In the houses they investigated, roofs were the most common failures. Those roof systems most often failed due to lack of proper sheathing nailing.

Wind – and earthquake-resistant framing are important skills for lead framers, and essential to those in susceptible parts of the country. Building codes, along with the designs architects and engineers create to meet code requirements, specify the framing for wind and earthquake resistance. The lead framer must take that information, along with data from connector manufacturers, and ensure that those requirements are met.

Roof failure as a result of Hurricane Andrew

Hold-Downs

Hold-downs are connections commonly used for foundations, wall-to-wall connections, wall-to – concrete connections, and wall or floor-to-drag strut. Hold-downs are also called anchor downs and tie-downs. They can be difficult to install, but if you plan ahead and install as you go, the job is more manageable. Hold-downs that attach walls to the concrete foundation are typically attached to bolts already in the concrete. These bolts are generally set in place by the foundation crew. Sometimes they won’t be set in the right place.

You will want to locate the hold-down as close to the end of the shear wall as possible. If the bolt is already in the concrete, you will have to locate a hold-down on either side of the bolt. When considering the location, be aware of how it relates to what is on the floor above it; you don’t want, for example, the hold-down coming up in a door or window.

You should also allow enough space to install and tighten nuts and bolts.

When to Install Hold-Downs

Although it is common to wait until the building is framed to install the hold-downs, waiting can also present problems, such as studs that are already nailed in place where you want to install the hold­downs, sheathing that is hard to nail because it may be on the exterior of a second or higher floor, and possible pipes or wires running in the stud cavity.

It is helpful to install the hold-down studs as you build the walls. The layout framer should detail the hold-down studs while detailing the wall plates, and should also drill the plates for the anchor bolt or the threaded rods. If an upper floor is involved, the framer should also drill down through the subfloor sheathing and the top and double plate of the wall on the floor below. The wall builder should drill the

studs before nailing them into the wall. When the wall sheathing is installed, make sure it is nailed to the hold-down studs using the same nailing pattern that was used for edge nailing. (See “Hold-Down Nailing" illustration.)

Install the hold-downs and bolts, and washers and nuts, as soon as possible. Note, too, that when installing hold-downs after the walls are built, it is more productive to do an entire floor at one time. If the anchor bolts in the concrete do not extend high enough, a coupler nut can be used to extend the length. (See “Coupler Nuts Can Extend Anchor Bolts" illustration.)

As noted previously, the holes drilled for the bolts attaching the hold-down to the studs should not be more than!/іб” bigger than the bolts. However, it is acceptable to oversize the holes you drill for the threaded rod that passes between the floors. This will make installation easier without affecting
strength. (See “Drill Hole Size for Hold-Downs" illustration.)

With all nail-on connection hardware, it is important to use the right size nail. Hardware manufacturer’s catalogs indicate nail size appropriate for each piece of hardware. Most catalogs also give some options for nail use.

Hold-downs

Drill Hole Size for Hold-Downs

Drill holes no more than /16" bigger than bolts to maintain strength.

Diaphragm Framing Tasks of Particular Concern

• Nail spacing—The nailing pattern for nailing the sheathing to the intermediate framing members is usually the standard 12" O. C. It is the edge nailing that changes to increase the strength.

• Penetration—The nail must not penetrate the sheathing’s outside veneer.

Nail Penetration

3/8" minimum from nail to edge of sheathing

/8" minimum gap

• Nail size—The nail sizes will vary based on the engineer’s design, or code requirements. Check the specified thickness and length.

• Blocking—It is common to have blocking in the joist space that runs parallel to the exterior walls. It will be detailed on the plans if it is required. Blocking can also be used on the edges of the sheathing.

Connections

“Connectors" can refer to beams or other construction elements, but in most cases, connectors are hardware specifically designed for common framing connections. As part of the load path, connections have to be strong enough to transfer the forces of nature.

In the prescriptive code, the connections are made with anchor bolts to the foundation, and with nails to connect floor joists to the plates below them, wall bottom plates to floors, and rafters or trusses to wall plates.

In non-prescriptive design, there are many ways to achieve the required force transfer between the shear walls, diaphragms, and foundation. The most common method involves metal connectors, which are produced by many companies. The Simpson Strong-Tie Company, because of its work in developing, testing, and cataloging connectors, is often referenced in building plans. Simpson Strong – Tie connector catalog numbers will be used in the balance of this book. Please note that substitutes with equivalent strength are available.

There are connectors made for just about every type of connection you can think of. As the framer in charge, however, it is not your job to decide on the type of connector, but rather to use correctly the connector that is specified. The best way to do this is to read the specifications in the connector catalog. Following is an illustration from a Simpson Strong-Tie Catalog, and a good example of instructions for installing hold-downs. You can reference the connectors at www. strongtie. com.

There are different connectors for the variety of different framing details, but only four common areas of connection:

• Foundation

• Wall-to-wall

• Roof-to-wall

• Foundation-to-top-of-the-top-wall

Important Points for Connection Framing

• Install all connectors per catalog instructions.

• Drill holes no more than VW bigger than bolts.

• Use washers next to wood.

• Fill all nail holes unless using catalog specifications.

• Know that the connection is only as strong as the weakest side. Make sure to space and nail each side the same. (See “Equal Nailing" illustration later in this chapter.)

• Be aware that some connectors have different-shaped nail holes. The different­shaped holes have different meaning, as illustrated in “Nail Hole Shapes" later in this chapter.